Quick Links

Español | Available From: Grainger US Acklands Grainger Grainger Mexico

Header

Navigation

Content

Item Details - 5DVN0

DaytonCentrifugal Belt-Drive Upblast Wall-Mount Exhaust Ventilator

Designed for use in restaurants, schools, commercial, and industrial applications to exhaust contaminated air from kitchen range hoods, up and away from the roof. Leakproof, spun aluminum construction features a fully rolled windband for increased stability. Select unit with drive package.

  • Aluminum backward inclined, nonoverloading centrifugal wheel design
  • Maximum inlet air temperature: 300º F
  • NEMA 1 junction box located in motor enclosure
  • Optional NEMA 1 and 4 disconnects available
  • Sealed pillow block bearings
  • UL/cUL 705 Listed for Power Ventilators
  • UL/cUL 762 Listed for Restaurant Exhaust Appliances
  • Air handling quality bearings meet minimum of L10-100,000 hours

Agency Compliance

Performance

Motor HPMax BHPFan RPMCFM @
0.000'' SP0.125'' SP0.250'' SP0.375'' SP0.500'' SP0.625'' SP0.750'' SP0.875'' SP1.000'' SP1.250'' SP1.500'' SP
1/4
0.26
875
CFM
Sones
1/3
0.35
965
CFM
Sones
1/2
0.54
1110
CFM
Sones
3/4
0.79
1265
CFM
Sones
1
1.05
1390
CFM
Sones
0.000'' SP0.125'' SP0.250'' SP0.375'' SP0.500'' SP0.625'' SP0.750'' SP0.875'' SP1.000'' SP1.250'' SP1.500'' SP
251523622177197417441365
11.010.610.19.99.79.7
2774263724772300210918931584
12.412.011.511.210.810.610.5
319130722941279626412475229720941770
15.014.614.213.813.513.112.912.612.2
3636353234263301317230362894274625832163
18.518.117.717.216.816.516.316.115.815.2
39963901380636983584346433403213307827852394
22.021.021.020.019.919.619.419.219.018.618.0
Agency Compliance

Dayton Electric Mfg. Co. certifies that the ventilators shown herein are licensed to bear the AMCA seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program.

Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels.

Catalog 405, January 2010

Recommended Accessories

Adapter
6KWJ6
Item
Thermostat Switch
2E940
Item

Product Specifications (Glossary)

Agency Compliance [?]
  • UL/cUL 762
  • AMCA Sound & Air
Assembled [?]FALSE
Base Diameter [?]22 1/8 in
Bearing Type [?]Sealed Pillow Block
CFM [?]1,365 to 3,996 ft3/min
Damper Width x Damper Height [?]15 x 15 in
Drive Package Description [?]Drives By Others
Drive Type [?]Belt Drive
Fan DescriptionExhaust Fan
Height [?]28 7/8 in
Horsepower [?] 1/4 to 1 hp
Housing Material [?]Spun Aluminum
Impeller Diameter (Nom.) [?]16 in
Impeller Material [?]Aluminum
Impeller Type [?]Backward Inclined Centrifugal
Includes [?]
  • NEMA 1 Junction Box
  • Mounting Plate
Max Inlet Temp [?]300 °F
Model DescriptionCentrifugal Belt-Drive Upblast Wall-Mount Exhaust Ventilator
Mounting Location [?]Wall
Overall Diameter [?]28 7/8 in
Recommended Damper Size15 x 15
Shaft Diameter [?] 3/4 in
Speed Controllable [?]No
TypeCentrifugal Belt-Drive Upblast, Less Drive Package
Warranty Length [?]1 Year

Footer