Download PDF for Print 11/22/2024

Centrifugal Belt-Drive In-Line Duct Blower

Item

Designed for indoor clean air applications including intake, exhaust, return, or make-up air systems in industrial or commercial buildings. Rugged construction allows fan to be installed in ductwork either horizontally or vertically. Duct collars provide easy duct connections. Access panels are included on each side of the unit.

  • Aluminum backward inclined, nonoverloading centrifugal wheel design
  • UL/cUL 705 Listed for Power Ventilators
  • Maximum inlet air temperature: 160º F
  • Bearing and motor cover provide longer service life
  • Regreaseable pillow block bearings
Item
ABCD
23 in22 in19 7/8 in1 in
EFG
18 3/5 in16 in12 3/8 in

Performance Characteristics

Item

Construction Features

Impeller Diameter (Typ.)14 in
Impeller TypeBackward Inclined Centrifugal
Impeller MaterialAluminum
Max Inlet Temp160 °F
Bearing TypeRegreaseable Pillow Block
Drive Package DescriptionDrives By Others
Warranty Length1 Year

Air & Sound Performance

Motor HPMax BHPFan RPMCFM @0.000'' SP0.125'' SP0.250'' SP0.375'' SP0.500'' SP0.625'' SP0.750'' SP0.875'' SP1.000'' SP1.250'' SP1.500'' SP1.750'' SP2.000'' SP2.250'' SP2.500'' SP2.750'' SP3.000'' SP
1/40.261318CFM1546148414171340125211551039866
Sones13.413.012.411.811.211.111.010.8
1/30.351455CFM170716501591152714521373128411821062
Sones14.914.814.213.813.413.012.812.712.5
1/20.521660CFM1948189818471794173716711601153014491256
Sones17.517.517.016.716.416.115.915.715.515.0
3/40.791908CFM223921952152210620602011195818961836170615531370
Sones21.021.020.020.019.719.419.118.818.417.817.116.8
11.052098CFM24622422238323422301225922132166211120011882174415851306
Sones25.025.025.024.024.023.023.022.022.021.020.020.019.819.5
1 1/21.572399CFM28152780274627112676263926032566252524372339224421342013188517321381
Sones30.030.030.030.030.030.029.029.028.027.026.025.024.024.023.023.023.0
22.102643CFM31013070303830072976294329102877284327712691260125152423232222102092
Sones32.033.033.033.033.034.033.033.033.032.031.030.029.028.028.027.026.0

Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (BHP) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: Free inlet hemispherical fan sone levels.

Agency Compliance

Dayton Electric Mfg. Co. certifies that the blowers shown herein are licensed to bear the AMCA seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program.

AMCA Sound & Air
Agency Compliance
UL/cUL 705
Agency Compliance