Centrifugal Belt-Drive In-Line Duct Blower

Item

Designed for indoor clean air applications including intake, exhaust, return, or make-up air systems in industrial or commercial buildings. Rugged construction allows fan to be installed in ductwork either horizontally or vertically. Duct collars provide easy duct connections. Access panels are included on each side of the unit.

  • Aluminum backward inclined, nonoverloading centrifugal wheel design
  • UL/cUL 705 Listed for Power Ventilators
  • Maximum inlet air temperature: 160º F
  • Bearing and motor cover provide longer service life
  • Regreaseable pillow block bearings
Item
ABCD
39 in34 in34 7/8 in1 1/2 in
EFG
25 3/5 in18 in13 3/4 in

Performance Characteristics

Item

Construction Features

Impeller Diameter (Typ.)24 in
Impeller TypeBackward Inclined Centrifugal
Impeller MaterialAluminum
Max Inlet Temp160 °F
Bearing TypeRegreaseable Pillow Block
Drive Package DescriptionDrives By Others
Warranty Length1 Year

Air & Sound Performance

Motor HPMax BHPFan RPMCFM @0.000'' SP0.125'' SP0.250'' SP0.375'' SP0.500'' SP0.625'' SP0.750'' SP0.875'' SP1.000'' SP1.250'' SP1.500'' SP1.750'' SP2.000'' SP2.250'' SP2.500'' SP2.750'' SP3.000'' SP
11.05822CFM541052485086487446594419416738933516
Sones16.616.416.015.615.215.014.814.614.3
1 1/21.57940CFM6186604559045747555953715167495547304173
Sones19.619.419.118.718.117.517.317.116.916.3
22.101035CFM681266836555642662666095592457425550514646323791
Sones22.022.021.021.020.019.919.419.118.918.618.317.7
33.131182CFM77797667755474427329718970396889674064116065570551984520
Sones26.026.026.025.025.024.023.023.022.022.022.021.021.021.0
55.191399CFM92079112901789228827873286358509838281307873758973016997668762445745
Sones32.033.033.033.033.032.031.030.030.029.027.026.025.025.025.024.024.0
7 1/27.841610CFM10,59610,51310,43110,34810,26610,18310,10010,018993297129492927390478800855482968031
Sones41.042.043.044.043.043.043.041.040.038.038.037.034.031.030.030.029.0

Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (BHP) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: Free inlet hemispherical fan sone levels.

Agency Compliance

Dayton Electric Mfg. Co. certifies that the blowers shown herein are licensed to bear the AMCA seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program.

AMCA Sound & Air
Agency Compliance
UL/cUL 705