Download PDF for Print 11/23/2024

Assembled Centrifugal Belt-Drive Upblast Exhaust Ventilator

Item

Designed for use in restaurants, schools, commercial, and industrial applications to exhaust contaminated air from kitchen range hoods, up and away from the roof. Leakproof, spun aluminum construction features a fully rolled windband for increased stability.

  • Aluminum backward inclined, nonoverloading centrifugal wheel design
  • Maximum inlet air temperature: 300º F
  • NEMA 1 junction box located in motor enclosure
  • Optional NEMA 1 and 4 disconnects available
  • Sealed pillow block bearings
  • UL/cUL 705 Listed for Power Ventilators
  • UL/cUL 762 Listed for Restaurant Exhaust Appliances
  • Air handling quality bearings meet minimum of L10-100,000 hours
Item
ABCD
26 in28 7/8 in26 3/8 in19 3/8 in

Performance Characteristics

Item

Construction Features

Impeller Diameter (Typ.)16 1/2 in
Impeller TypeBackward Inclined Centrifugal
Impeller MaterialAluminum
Max Inlet Temp300 °F
Bearing TypeSealed Pillow Block
Drive Package DescriptionDrives Assembled
Warranty Length1 Year

Motor Information

Motor Item Number4YU30
Voltage115/208-230
Hertz (Cycle)60 Hz
Motor Phase1
Motor EnclosureOpen Drip Proof
RPM1,725 rpm
Full Load Amps12.8/6.4-6.4

Other Components

ComponentDescriptionItem #
Fan DescriptionExhaust Fan
BeltAX22 (QTY: 1)3VU41
Driver Sheave1VP40x5/83X264
Driven SheaveBK55H3X587
Driven BushingH x 3/43X573

Air & Sound Performance

Motor HPMax BHPFan RPMCFM @0.000'' SP0.125'' SP0.250'' SP0.375'' SP0.500'' SP0.625'' SP0.750'' SP0.875'' SP1.000'' SP1.250'' SP1.500'' SP
11.051390CFM39963901380636983584346433403213307827852394
Sones22.021.021.020.019.919.619.419.219.018.618.0

Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels.

Catalog 405, January 2010

Operating Range of Drive Package

Turns Open01/211 1/222 2/133 1/244 1/25
Approx. FRPM1361132412861249121211751137110010631025

Agency Compliance

Dayton Electric Mfg. Co. certifies that the ventilators shown herein are licensed to bear the AMCA seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program.

AMCA Sound & Air
Agency Compliance
UL/cUL 762
Agency Compliance
CSA Certified Motor