Utility Exhaust Belt-Drive Blower

Item

Designed for commercial kitchen exhaust or industrial spark resistant applications requiring high volumes of air at high static pressures. Suitable for ducted exhaust, supply or return-air applications. Constructed out of heavy gauge steel with polyester gray coating. The scroll is welded, has a bolted access door and 1 inch threaded drain connection for easy cleaning.

  • Maximum inlet air temperature: 300º F
  • UL/cUL 762 Listed for Restaurant Exhaust Appliances
  • Polyester gray coating
  • Backward incline nonoverloading aluminum wheel
  • Aluminum rub ring
  • Bolted access door
Item
ABCE
13 in9 5/8 in15 1/2 in22 1/4 in
FGHJ
21 3/8 in13 in13 1/4 in23 3/16 in
KMN
9 3/4 in15 1/8 in16 in

Performance Characteristics

Item

Construction Features

Impeller Diameter (Typ.)12 1/4 in
Impeller TypeBackward Inclined Centrifugal
Impeller MaterialAluminum
Max Inlet Temp300 °F
Bearing TypeBall
Drive Package DescriptionDrives By Others
Warranty Length1 Year

Air & Sound Performance

Motor HPMax BHPFan RPMCFM @0.000'' SP0.125'' SP0.250'' SP0.375'' SP0.500'' SP0.625'' SP0.750'' SP0.875'' SP1.000'' SP1.250'' SP1.500'' SP1.750'' SP2.000'' SP2.250'' SP2.500'' SP2.750'' SP3.000'' SP
1/40.251501CFM15481494144413871324125811761093968
Sones11.811.411.010.610.310.09.79.49.0
1/30.331643CFM1694164515971553149514381376130112261005
Sones13.212.812.512.211.811.411.210.910.710.0
1/20.501889CFM194819051862182317831733168316331578144712961065
Sones15.915.615.315.014.814.514.214.013.813.312.812.3
3/40.752159CFM22272189215121132081204820041960191718281715160014481246906
Sones19.118.918.718.418.218.017.817.617.417.016.516.115.515.014.7
11.002373CFM24472413237923442311228222532213217220932013191018061702153013461024
Sones21.021.021.020.020.020.020.019.819.719.318.918.518.117.617.016.616.3
1 1/21.502716CFM28012771274127112681265126262600257425032434236422932202211120201928
Sones25.025.025.025.024.024.024.024.024.023.023.023.022.022.022.021.021.0
21.982991CFM30853057303030032976294829212898287528252761269826352571250024182335
Sones29.029.029.029.028.028.028.028.028.027.027.027.026.026.026.025.025.0

Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (BHP) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified ratings Seal applies to air performance ratings only.