Axial Direct-Drive Downblast Exhaust Ventilator

Item

Designed for situations requiring the steady exhaust of air under low to moderate static pressures. Fully rolled baffle bead for stability and ease of transport with spun aluminum hood construction. Galvanized steel venturi, inlet and supports.

  • Maximum inlet air temperature: 120º F
  • NEMA 1 junction box located in motor enclosure
  • Optional NEMA 1 and 4 disconnects available
  • UL/cUL 705 Listed for Power Ventilators
  • Wall or roof mountable
Item
ABCD
22 in28 5/8 in16 1/2 in6 1/4 in

Performance Characteristics

Item

Construction Features

Impeller Diameter (Typ.)12 in
Impeller TypePropeller
Impeller MaterialAluminum
Number of Blades4
Max Inlet Temp120 °F
Warranty Length1 Year

Motor Information

Motor Item Number5BE62
Voltage115
Hertz (Cycle)60 Hz
Motor Phase1
Motor EnclosureOpen Air-Over
RPM1,140 rpm
Full Load Amps2.2

Air & Sound Performance

Motor HPMax BHPFan RPMCFM @0.000'' SP0.125'' SP0.250'' SP0.375'' SP
1/60.051140CFM1014803376144
Sones5.15.17.48.6

Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings include the effects of a birdscreen in the airstream. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical fan sone levels.

Catalog 405, January 2010

Agency Compliance

Dayton Electric Mfg. Co. certifies that the ventilators shown herein are licensed to bear the AMCA seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program.

AMCA Sound & Air
Agency Compliance
UL/cUL 705
Agency Compliance