Download PDF for Print 11/22/2024

Centrifugal Belt-Drive In-Line Duct Blower

Item

Designed for indoor clean air applications including intake, exhaust, return, or make-up air systems in industrial or commercial buildings. Rugged construction allows fan to be installed in ductwork either horizontally or vertically. Duct collars provide easy duct connections. Access panels are included on each side of the unit.

  • Aluminum backward inclined, nonoverloading centrifugal wheel design
  • UL/cUL 705 Listed for Power Ventilators
  • Maximum inlet air temperature: 160º F
  • Bearing and motor cover provide longer service life
  • Regreaseable pillow block bearings
Item
ABCD
23 in22 in19 7/8 in1 in
EFG
18 3/5 in16 in12 3/8 in

Performance Characteristics

Item

Construction Features

Impeller Diameter (Typ.)14 in
Impeller TypeBackward Inclined Centrifugal
Impeller MaterialAluminum
Max Inlet Temp160 °F
Bearing TypeRegreaseable Pillow Block
Drive Package DescriptionDrives By Others
Warranty Length1 Year

Air & Sound Performance

Motor HPMax BHPFan RPMCFM @0.000'' SP0.125'' SP0.250'' SP0.375'' SP0.500'' SP0.625'' SP0.750'' SP0.875'' SP1.000'' SP1.250'' SP1.500'' SP1.750'' SP2.000'' SP2.250'' SP2.500'' SP2.750'' SP
1/40.11800CFM150913621185860
Sones5.96.36.75.8
1/40.261076CFM202919271810168115381311
Sones10.810.710.710.810.28.2
1/30.351185CFM22352142203919271807166714631098
Sones12.312.111.912.012.011.610.69.2
1/20.521356CFM255724762392229721972095197918271636
Sones14.514.213.913.813.813.813.813.813.8
3/40.791553CFM29292858278727082626253924492355225319641447
Sones16.416.216.016.016.015.815.615.415.314.713.9
11.051709CFM322331593094302829532878279827172635245121771752
Sones18.618.218.017.917.917.817.717.417.216.816.115.1
1 1/21.571956CFM36893633357635203461339533303264319330502894270524572089
Sones25.024.023.024.024.024.024.023.023.023.022.021.020.019.2
22.102153CFM4060400939583907385638003741368136223494336533253078286126272260
Sones31.030.030.030.031.032.031.030.030.029.028.028.027.026.025.023.0

Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (BHP) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: Free inlet hemispherical fan sone levels.

Catalog 405, January 2010

Agency Compliance

Dayton Electric Mfg. Co. certifies that the blowers shown herein are licensed to bear the AMCA seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program.

AMCA Sound & Air
Agency Compliance
UL/cUL 705
Agency Compliance