Download PDF for Print 11/22/2024

Centrifugal Belt-Drive In-Line Duct Blower

Item

Designed for indoor clean air applications including intake, exhaust, return, or make-up air systems in industrial or commercial buildings. Rugged construction allows fan to be installed in ductwork either horizontally or vertically. Duct collars provide easy duct connections. Access panels are included on each side of the unit.

  • Aluminum backward inclined, nonoverloading centrifugal wheel design
  • UL/cUL 705 Listed for Power Ventilators
  • Maximum inlet air temperature: 160º F
  • Bearing and motor cover provide longer service life
  • Regreaseable pillow block bearings
Item
ABCD
26 in26 in22 7/8 in1 in
EFG
21 in17 in13 3/8 in

Performance Characteristics

Item

Construction Features

Impeller Diameter (Typ.)16 in
Impeller TypeBackward Inclined Centrifugal
Impeller MaterialAluminum
Max Inlet Temp160 °F
Bearing TypeRegreaseable Pillow Block
Drive Package DescriptionDrives By Others
Warranty Length1 Year

Air & Sound Performance

Motor HPMax BHPFan RPMCFM @0.000'' SP0.125'' SP0.250'' SP0.375'' SP0.500'' SP0.625'' SP0.750'' SP0.875'' SP1.000'' SP1.250'' SP1.500'' SP1.750'' SP2.000'' SP2.250'' SP2.500'' SP2.750'' SP3.000'' SP
1/40.26873CFM25202373220920151759
Sones9.18.88.68.48.2
1/30.35962CFM277726432504233921501893
Sones10.39.99.69.59.39.2
1/20.521101CFM31793061294428122665250423012044
Sones12.612.412.111.811.411.311.211.1
3/40.781261CFM3641353834363333321230872946279526112071
Sones16.015.515.114.814.614.514.413.813.211.8
11.051387CFM40043911381837253628351534023274314628152311
Sones18.518.017.517.317.217.016.916.716.114.713.1
1 1/21.561588CFM4585450344224341425941784079398038803656338930552566
Sones23.022.022.021.021.022.022.022.021.020.018.917.516.1
22.081748CFM50474973489948254751467746034514442542404037380235282185
Sones29.028.027.026.026.026.027.027.027.026.024.023.022.019.9
33.122001CFM57775713564855845519545453905325526051034946477445964392416038833566
Sones42.040.038.037.036.036.036.037.038.039.038.036.034.031.029.027.026.0

Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (BHP) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: Free inlet hemispherical fan sone levels.

Catalog 405, January 2010

Agency Compliance

Dayton Electric Mfg. Co. certifies that the blowers shown herein are licensed to bear the AMCA seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program.

AMCA Sound & Air
Agency Compliance
UL/cUL 705
Agency Compliance