Centrifugal Belt-Drive In-Line Duct Blower

Item

Designed for indoor clean air applications including intake, exhaust, return, or make-up air systems in industrial or commercial buildings. Rugged construction allows fan to be installed in ductwork either horizontally or vertically. Duct collars provide easy duct connections. Access panels are included on each side of the unit.

  • Aluminum backward inclined, nonoverloading centrifugal wheel design
  • UL/cUL 705 Listed for Power Ventilators
  • Maximum inlet air temperature: 160º F
  • Bearing and motor cover provide longer service life
  • Regreaseable pillow block bearings
Item
ABCD
32 in32 in27 7/8 in1 1/2 in
EFG
25 3/5 in18 in13 3/4 in

Performance Characteristics

Item

Construction Features

Impeller Diameter (Typ.)20 in
Impeller TypeBackward Inclined Centrifugal
Impeller MaterialAluminum
Max Inlet Temp160 °F
Bearing TypeRegreaseable Pillow Block
Drive Package DescriptionDrives By Others
Warranty Length1 Year

Air & Sound Performance

Motor HPMax BHPFan RPMCFM @0.000'' SP0.125'' SP0.250'' SP0.375'' SP0.500'' SP0.625'' SP0.750'' SP0.875'' SP1.000'' SP1.250'' SP1.500'' SP1.750'' SP2.000'' SP
1/30.34660CFM35693315301826702042
Sones12.211.711.210.810.5
1/20.52756CFM408838673624334830362572
Sones13.312.712.011.811.712.0
3/40.79865CFM46784484428540613812354432392516
Sones14.514.113.713.413.113.013.013.9
11.04952CFM514849724796459843914159391636463203
Sones16.015.715.515.215.115.014.914.514.4
1 1/21.571090CFM5895574155875430525350754874467244523878
Sones19.319.118.918.818.718.618.518.618.717.3
22.091200CFM64906350621060705920575855975416523348364316
Sones22.022.022.022.021.021.021.021.021.021.019.8
33.121373CFM7425730371817059693668066665652463836063573853634839
Sones28.027.027.026.026.026.026.026.026.025.025.025.024.0

Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (BHP) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: Free inlet hemispherical fan sone levels.

Catalog 405, January 2010

Agency Compliance

Dayton Electric Mfg. Co. certifies that the blowers shown herein are licensed to bear the AMCA seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program.

AMCA Sound & Air
Agency Compliance
UL/cUL 705
Agency Compliance