Download PDF for Print 12/4/2024

Centrifugal Belt-Drive Downblast Exhaust Ventilator

Item

Designed to meet the general clean air exhaust requirements for industrial and commercial buildings. Features a fully rolled windband bead for increased stability and easy transport. Fresh outside air is drawn in under the motor cover to maximize motor life.

  • Aluminum backward inclined, nonoverloading centrifugal wheel design
  • Maximum inlet air temperature: 180º F
  • NEMA 1 junction box located in motor enclosure
  • Optional NEMA 1 and 4 disconnects available
  • Regreaseable pillow block bearings
  • Air handling quality bearings meet minimum of L10-100,000 hours
  • UL/cUL 705 Listed for Power Ventilators
Item
ABCD
34 in42 3/4 in38 3/8 in5 3/4 in

Performance Characteristics

Item

Construction Features

Impeller Diameter (Typ.)24 1/2 in
Impeller TypeBackward Inclined Centrifugal
Impeller MaterialAluminum
Max Inlet Temp180 °F
Bearing TypeRegreaseable Pillow Block
Drive Package DescriptionDrives By Others
Warranty Length1 Year

Air & Sound Performance

Motor HPMax BHPFan RPMCFM @0.000'' SP0.125'' SP0.250'' SP0.375'' SP0.500'' SP0.625'' SP0.750'' SP0.875'' SP1.000'' SP1.250'' SP1.500'' SP
1/40.26500CFM3799351231322542
Sones8.88.47.97.5
1/30.35550CFM41793924362931582526
Sones10.09.68.98.48.0
1/20.55640CFM486346544403412037023208
Sones13.012.812.111.210.59.7
3/40.75710CFM53955206499047624459407736332974
Sones15.014.914.413.612.812.111.210.3
11.07800CFM607959115732553053265049471643603929
Sones16.616.416.115.615.214.614.213.412.5
1 1/21.50895CFM6801665165016323614259605723543551224401
Sones19.419.118.818.518.218.017.617.316.915.5
22.00985CFM74857349721270626898673465686368610755484883
Sones23.023.023.022.022.022.02.021.021.020.019.0

Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen in the airstream. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels.

Catalog 405, January 2010

Agency Compliance

Dayton Electric Mfg. Co. certifies that the ventilators shown herein are licensed to bear the AMCA seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program.

AMCA Sound & Air
Agency Compliance
UL/cUL 705
Agency Compliance