Download PDF for Print 11/23/2024

Centrifugal Belt-Drive Downblast Exhaust Ventilator

Item

Designed to meet the general clean air exhaust requirements for industrial and commercial buildings. Features a fully rolled windband bead for increased stability and easy transport. Fresh outside air is drawn in under the motor cover to maximize motor life.

  • Aluminum backward inclined, nonoverloading centrifugal wheel design
  • Maximum inlet air temperature: 180º F
  • NEMA 1 junction box located in motor enclosure
  • Optional NEMA 1 and 4 disconnects available
  • Regreaseable pillow block bearings
  • Air handling quality bearings meet minimum of L10-100,000 hours
  • UL/cUL 705 Listed for Power Ventilators
Item
ABCD
42 in50 in36 in8 1/4 in

Performance Characteristics

Item

Construction Features

Impeller Diameter (Typ.)26 1/2 in
Impeller TypeBackward Inclined Centrifugal
Impeller MaterialAluminum
Max Inlet Temp180 °F
Bearing TypeRegreaseable Pillow Block
Drive Package DescriptionDrives By Others
Warranty Length1 Year

Air & Sound Performance

Motor HPMax BHPFan RPMCFM @0.000'' SP0.125'' SP0.250'' SP0.375'' SP0.500'' SP0.625'' SP0.750'' SP0.875'' SP1.000'' SP1.250'' SP1.500'' SP1.750'' SP2.000'' SP
1/20.54465CFM600555705063448437452322
Sones11.410.910.410.19.69.5
3/40.75520CFM6716632458985413486941903008
Sones12.912.111.310.910.39.69.4
11.04580CFM74917137677563635912541848263931
Sones14.413.713.012.612.211.611.010.3
1 1/21.57665CFM8588827879797637727468846474601654653608
Sones16.716.215.815.315.014.614.213.813.312.8
22.13735CFM94939212893886528335800176497280687859164236
Sones18.918.618.317.917.617.216.816.516.215.614.9
33.12835CFM10,78410,53710,29210,055979495149225892786067932715760244294
Sones23.023.022.022.022.022.021.021.020.019.919.718.718.6

Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen in the airstream. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels.

Catalog 405, January 2010

Agency Compliance

Dayton Electric Mfg. Co. certifies that the ventilators shown herein are licensed to bear the AMCA seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program.

AMCA Sound & Air
Agency Compliance
UL/cUL 705
Agency Compliance