Download PDF for Print 11/24/2024

Centrifugal Belt-Drive In-Line Duct Blower

Item

Designed for indoor clean air applications including intake, exhaust, return, or make-up air systems in industrial or commercial buildings. Rugged construction allows fan to be installed in ductwork either horizontally or vertically. Duct collars provide easy duct connections. Access panels are included on each side of the unit.

  • Aluminum backward inclined, nonoverloading centrifugal wheel design
  • UL/cUL 705 Listed for Power Ventilators
  • Maximum inlet air temperature: 160º F
  • Bearing and motor cover provide longer service life
  • Sealed pillow block bearings
Item
ABCD
19 in21 in13 7/8 in1 in
EFG
17 3/8 in16 in12 1/2 in

Performance Characteristics

Item

Construction Features

Impeller Diameter (Typ.)13 1/8 in
Impeller TypeBackward Inclined Centrifugal
Impeller MaterialAluminum
Max Inlet Temp160 °F
Bearing TypeSealed Pillow Block
Drive Package DescriptionDrives By Others
Warranty Length1 Year

Air & Sound Performance

Motor HPMax BHPFan RPMCFM @0.000'' SP0.125'' SP0.250'' SP0.375'' SP0.500'' SP0.625'' SP0.750'' SP0.875'' SP1.000'' SP1.250'' SP1.500'' SP1.750'' SP2.000'' SP2.250'' SP2.500'' SP
1/40.261366CFM1548147013911310122511301018840
Sones11.210.911.010.510.510.29.99.2
1/30.351508CFM170916391567149414211342125611601032
Sones12.812.512.512.211.711.411.110.710.3
1/20.521721CFM1950188918271763170016351567149714181235
Sones15.915.115.715.214.514.013.813.613.512.4
3/40.791979CFM224321892135208120261970191518581798167015271321
Sones19.819.119.119.018.417.917.617.417.016.515.814.6
11.052174CFM2434241523662317226722172166211620651956183917151557
Sones23.023.023.023.022.021.021.021.021.019.719.018.517.6
1 1/21.572488CFM282027772734269226482605256125172473238422912196208919811848
Sones31.031.030.030.029.028.027.026.026.027.026.025.024.023.023.0

Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (BHP) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: Free inlet hemispherical fan sone levels.

Agency Compliance

Dayton Electric Mfg. Co. certifies that the blowers shown herein are licensed to bear the AMCA seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program.

AMCA Sound & Air
Agency Compliance
UL/cUL 705
Agency Compliance